Moten found “no evident sign of burning, bulging or distortion of the boiler" following the pressure buildup on May 7 and 8.
According to the fire marshal, "one reason the boiler overheated was that an automatic control for the heating system had been bypassed because of a malfunction in the control.”
In order to prevent repeat occurences of the same type of situation, Frese suggested that a staff policy be established "to require immediate replacement of control mechanisms when the heating system is in use until the control mechanism could be repaired or replaced.”
The fire marshal’s report emphasizes that maintenance recommendations from Moten should be implemented as soon as practicable.
Moten, an employee of the insurance company which carries the policy on the Rappahannock schools, suggested that (1) fire surfaces of the boiler be kept thoroughly cleaned of soot and ashes to reduce deterioration from external corrosion when the boiler is idle and to reduce fuel